When you need more of everything.
The E.A. Group Series 1200 PDU has been designed with space, adaptability and safety in mind. It effectively manages large scale supply to branch circuit distribution, such as the Series 400 PDU. Its "I-line" distribution ensures first-rate quality and unmatched protection for on-site technicians.
download sales sheet (s1200 PDU) >
key features >
specifications >
The E.A. Group Series 1200 PDU is a compact electrical enclosure that effectively manages large scale supply to branch circuit distribution, such as the Series 400 PDU.
The Series 1200 PDU has been designed with a focus on adaptability and safety. The “I-line” distribution panel delivers first-rate quality and un-matched protection for on-site technicians. This style of real-world design, along with a variety of transformation, metering, and wiring options make the Series 1200 PDU an exceptional solution for today's ever-changing data centres.
KEY FEATURES
- Easily adaptable for any application through a variety of supply, distribution, and transformation options.
- Extensive monitoring and metering capabilities – network adaptable.
- Compact design accommodates ten 3-pole distribution breakers within a small footprint
- Copper bus on all power connections for maximum reliabiity.
- User-friendly installation and utilization.
- Industry standard components, attainable throughout North America.
- Cost effective, large-scale power distribution with small-scale adaptability.
- C.S.A. approved.
SPECIFICATIONS
Standard Models
- S1200-125: 125kVA – 1750 LBS
- S1200-150: 150kVA – 2000 LBS
- S1200-225: 225kVA – 2500 LBS
- S1200-NSE: >225kVA
NOTE: weights apply to standard PDUs only.
Standard Specifications
INPUT VOLTAGE: 600V, 3-phase, 3-wire
OUTPUT VOLTAGE: 120/208V, 3-phase, 4-wire
MAIN BREAKER: GE Spectra Series Digital RMS molded case breaker with 18kA sym. fault current rating
PANELBOARD: Sq.D 800A I-Line 30 circuit panel
TRANSFORMER: Harmonic cancellation transformer with 130°C temperature rise and 55dB sound level
FRAME DIMENSIONS: 36”W x 36”D x 75”H top and bottom input cabling
Optional Specifications
INPUT VOLTAGE: 480V, 3-phase, 3-wire
OUTPUT VOLTAGE: 600/347V or 480/278V, 3-phase, 4-wire
MAIN BREAKER: Breaker with up to 65kA sym. fault current
BRANCH BREAKERS: Sq.D I-Line thermomagnetic trip molded case breakers with up to 42kA sym. fault current rating
TRANSFORMER:
- Delta-wye isolation
- k13 rated
- k20 rated
- Harmonic cancellation 150°C rise
FRAME DIMENSIONS:
- 24”W x 36”D x 75”H top input cabling only
- Consult factory for restrictions
Additional Options
OVERHEAD CABLING MODEL:
- Input and output cabling enter and exit the top of the unit for facilities with no under-floor access
PML 7300 DIGITAL POWER METER:
- Indicates the real time output voltage, output current, kW total, kVA total, power factor, harmonic distortion, frequency and Kilowatt-hours
PML 7330 DIGITAL POWER METER:
- Indicates the real time output voltage, output current, kW total, kVA total, power factor, harmonic distortion, frequency and Kilowatt-hours
- Interface adaptability to third party devices and systems
- Two external input alarm points
- Multiple meter link with RS485 loop
- Ethernet port (optional)
- Monitors transformer temperature
- Local/remote alarm annunciation package available
EMERGENCY POWER OFF (E.P.O.):
- Provides local or remote E.P.O.
TRANSIENT VOLTAGE SURGE SUPPRESSION (T.V.S.S.):
- Protects downstream loads from dangerous voltage transients
- This device can be equipped with a transient counter, auxiliary contacts, and annunciation
- Available at 90kA and 150kA, surge capacity per-phase.
LOCKABLE FRONT DOORS:
- Provides security in unsecured areas.