Adaptable, flexible, and powerful, too.
It's extremely adaptable, and can easily manage power distribution and monitoring for today's most demanding computer facilities. Whether large or small, you'll find the Series 600 can manage a wide variety of transformation, metering, supply and distribution options.
download sales sheet (s600 PDU) >
key features >
specifications >
The E.A. Group Series 600 PDU is an extremely adaptable stand-alone electrical enclosure that effectively manages power distribution and monitoring for today's demanding computer facilities - large or small.
A wide variety of transformation, metering, supply and distribution options make the Series 600 PDU an exceptional solution for today's ever-changing data centres.
KEY FEATURES
- Easily adaptable for any application through a variety of supply, distribution, and transformation options
- Extensive monitoring and metering capabilities – network adaptable
- Hinged panel covers
- User-friendly installation and utilization
- Industry standard components, attainable throughout North America
- Readiness to incorporate the Series 400 sidecar
- Cost effective, large-scale power distribution with small-scale adaptability
- C.S.A. approved
SPECIFICATIONS
Standard Models
- S600-30: 30kVA – 700 LBS
- S600-45: 45kVA – 900 LBS
- S600-75: 75kVA – 1200 LBS
- S600-100: 100kVA – -1415 LBS
- S600-112.5: 112.5kVA – 1520 LBS
- S600-125: 125kVA – 1665 LBS
- S600-150: 150kVA – 1950 LBS
- S600-NSE: >150kVA
NOTE: weights apply to standard PDUs only.
Standard Specifications
INPUT VOLTAGE: 600V, 3-phase, 3-wire
OUTPUT VOLTAGE: 120/208V, 3-phase, 4-wire
MAIN BREAKER: GE Spectra Series Digital RMS molded case breaker with 14kA sym. fault current rating
PANELBOARD:
- Two 42-pole Sq.D type NQOD panels with two Sq.D 225A, Q2L thermomagnetic trip main breakers with 10kA sym. fault current rating
- 200% neutral bus
TRANSFORMER: Delta-wye isolation with 150°C operating temperature and electrostatic shield.
FRAME DIMENSIONS: 38”W x 32”D x 69”H
Optional Specifications
INPUT VOLTAGE: 480V, 3-phase, 3-wire
OUTPUT VOLTAGE: 120/208V, 3-phase, 4-wire
MAIN BREAKER: Available up to 65kA sym. fault current rating
PANELBOARD:
- 42 circuits (1 panel)
- 126 circuits (3 panels)
- 168 circuits (4 panels)
- bolt-on or plug-in breakers with up to 22kA sym. fault current rating
- GE type AQL panels
TRANSFORMER:
- k13 rated
- k20 rated
- Harmonic cancellation 150°C rise
- Harmonic cancellation 130°C rise
FRAME DIMENSIONS: 49”W x 32”D x 69”H 126 & 168 circuits
Additional Options
OVERHEAD CABLING MODEL:
- Input and output cabling enter and exit the top of the unit for facilities with no under-floor access
SIDECAR PDU:
- Expand your existing PDU to add additional circuits with the Series 400 Sidecar, which can be installed quickly with little or no downtime
PML 7300 DIGITAL POWER METER:
- Indicates the real time output voltage, output current, kW total, kVA total, power factor, harmonic distortion, frequency and Kilowatt-hours
PML 7330 DIGITAL POWER METER:
- Indicates the real time output voltage, output current, kW total, kVA total, power factor, harmonic distortion, frequency and Kilowatt-hours
- Interface adaptability to third party devices and systems.
- Two external input alarm points
- Multiple meter link with RS485 loop
- Ethernet port (optional)
- Monitors transformer temperature
- Local/remote alarm annunciation package available
EMERGENCY POWER OFF (E.P.O.):
- Provides local or remote E.P.O.
TRANSIENT VOLTAGE SURGE SUPPRESSION (T.V.S.S.):
- Protects downstream loads from dangerous voltage transients.
- This device can be equipped with a transient counter, auxiliary contacts, and annunciation
- Available at 90kA and 150kA, surge capacity per-phase.
ISOLATED GROUND FOR PDU AND SIDECARS:
- Includes isolated ground wiring of all panels (42 positions per panel board) and a central termination point that is factory bonded to the main ground
UNDER FLOOR JUNCTION BOXES:
- Includes all input wiring and 10’ of computer grade liquid tight flexible conduit terminated on power terminals in a NEMA 1 enclosure.